B2410

Read the instructions below then start the fault diagnostic procedure.

Symptom: The cabin mists up. Bad air in cabin. The perceived cabin temperature is too high compared to the set temperature.

B2410


Recirculation Motor. Short to B+

Recirculation Motor. Open Circuit / Short to Ground


Fault symptoms


• The cabin mists up.

• Bad air in cabin.

• The perceived cabin temperature is too high compared to the set temperature.


Conditions

The following conditions apply:


• A short to B+ is indicated when the output for the air recirculation motor is not activated and the voltage on pin 21 exceeds 9 V.

• A short to ground and open circuit is indicated when the output for the air recirculation motor is not activated and the voltage on pin 21 is below 3 V.

• Measured every 440 ms and 5 consecutive measurements are required to set a diagnostic trouble code.

• The diagnostic trouble code is deleted after the ignition has been switched on 20 times if the malfunction conditions have not been fulfilled.

• When the diagnostic trouble code has been set the output is switched off.