B2345
Read the instructions below then
start the fault diagnostic procedure.
Symptom: Perceived temperature in cabin too high or too low compared to the set temperature.
Mixed Air Sensor Right. Short to Ground
Mixed Air Sensor Right. Open Circuit / Short to B+
Fault symptoms
Perceived temperature in cabin too high or too low compared to the set temperature.
Conditions
The following conditions apply:
•
|
Open circuit or short circuit to B+ when the voltage on pin 25 is >4.9 V.
|
•
|
Short circuit to ground on pin is generated when the voltage on pin 25 is <0.1 V.
|
•
|
Measured every 40 ms, and 5 consecutive measurements are required to generate a diagnostic trouble code.
|
•
|
The diagnostic trouble code is deleted after the ignition has been switched on 20 times if the malfunction conditions have not been fulfilled.
|
•
|
When the diagnostic trouble code is generated the control module uses one substitute value.
|