Robinair 10324 Smart Cart and Robinair 17234 draining station
|
Robinair 10324 Smart Cart and Robinair 17234 draining station
|
Important
|
Draining of the system should be carried out on both the low-pressure and high-pressure sides simultaneously. A non-return valve in the inlet of the compressor's low-pressure side makes draining of only one side impossible.
|
|
1.
|
Using a snap-on coupling, connect the blue low-pressure hose to the low-pressure side of the AC system.
|
2.
|
Using a snap-on coupling, connect the red high-pressure hose to the high-pressure side of the AC system.
|
3.
|
Open the valves on both snap-on couplings by screwing in the knobs.
|
4.
|
Using the yellow hose, connect the pressure gauge stand's middle outlet to the draining station.
|
5.
|
Open the cocks on the blue low-pressure hose and the red high-pressure hose and the cock on the yellow hose connected to the pressure gauge stand's middle outlet.
|
6.
|
Open the blue cock ("Liquid") for liquid refrigerant and the red cock ("Gas") for gaseous refrigerant on the draining station's container.
|
7.
|
Start the draining station. When draining is finished, the draining station will switch off automatically.
|
8.
|
Close the cocks on the blue low-pressure hose, the red high-pressure hose and the yellow hose connected to the pressure gauge stand's middle outlet.
|
9.
|
Remove the yellow hose from the draining station. Draining is now finished and work on the AC unit can commence.
|