B1347
B1347 |
Blended-air sensor, shorting to ground
Conditions
B1347: Control module input pin 32, shorted to ground.
Diagnostic procedure
If diagnostic trouble code B1515 has been generated it should be dealt with first. See
1. |
Connect the ISAT and obtain a "MIXED AIR SENSOR" readout. The voltage should be within 1-4 V and change when the selected indoor temperature is changed.
|
2. |
Unplug the 10-pin connector (H10-5) and check the voltage across connector pins 9 and 10. It should be about 4.5 - 5 V. If it is not, proceed to point 4.
![]() |
4. |
Unplug the ACC control module's connector. Connect a BOB to the wiring and check the leads for continuity and/or shorting as follows:
![]() ![]() |
• |
across pin 14 of the ACC control module's connector and pin 9 of the sensor's connector H10-5
|
• |
across pin 32 of the ACC control module's connector and pin 10 of the sensor's connector H10-5.
![]() Rectify any faulty lead in the wiring. |
5. |
If the fault persists, proceed to section
![]() |