Robinair 10324 Smart Cart and Robinair 17234 draining station

Draining


Important

Draining of the system should be carried out on both the low-pressure and high-pressure sides simultaneously. A non-return valve in the inlet of the compressor's low-pressure side makes draining of only one side impossible.



1. Using a snap-on coupling, connect the blue low-pressure hose to the low-pressure side of the AC system.

2. Using a snap-on coupling, connect the red high-pressure hose to the high-pressure side of the AC system.

3. Open the valves on both snap-on couplings by screwing in the knobs.

4. Using the yellow hose, connect the pressure gauge stand's middle outlet to the draining station.

5. Open the cocks on the blue low-pressure hose and the red high-pressure hose and the cock on the yellow hose connected to the pressure gauge stand's middle outlet.

6. Open the blue cock ("Liquid") for liquid refrigerant and the red cock ("Gas") for gaseous refrigerant on the draining station's container.

7. Start the draining station. When draining is finished, the draining station will switch off automatically.

8. Close the cocks on the blue low-pressure hose, the red high-pressure hose and the yellow hose connected to the pressure gauge stand's middle outlet.

9. Remove the yellow hose from the draining station. Draining is now finished and work on the AC unit can commence.